Home » Generators, Inventory

(2) Cooper Superior Model 2408 + (2) MITSUBISHI Model RM 500G – GS12A2-PTK

28 May 2009 273 views
Item Number:
Make: Cooper Superior + Mitsubishi
Model: 2408 + 500G - GS12A2-PTK
Fuel Type: Natural Gas
   
# Of Units: 4
MW Each
MW Total: 3.3 (2.2 + 1)
Voltage:
Hertz: 60
RPM: 1200
$/kW:
   
Year:
Run Hours:
Rebuild Hours:
# Of Starts:
   
Unit Location:
Unit Price: $580,000 USD
   
More Info:  

(2) Low Hour Cooper Superior Model 2408
(2) Low Hour MITSUBISHI Model RM 500G - GS12A2-PTK

Package of All Four Units
Price $580,000

Cooper Superior Model 2408
Natural Gas Generator Sets
Packaged by Simpson Power Products LTD
1.1 MW Each (1375 kva)
2.2 MW Total
60 Hz
480 volts
1200 RPM
Total Run Hrs = 690 & 1089
Originally Shipped on 10th Day of 2000


1576 HP
Originally shipped to customer from Simpower on October of 2000
Units have not operated for two years now.
Used for a temporary power need.
Well maintained.
Functioning well at time of shutdown.
Owned by a municipality.
The core heaters have been kept on.
Generator Info
p.f. - .8
amp - 1654
Rotation - ccw
rpm - 1200
phase - 3
serial - bu5l3576
gen model - mtg 846
emi - 60088300

One engine serial number is: 340399

(2) MITSUBISHI Model RM 500G - GS12A2-PTK
NATURAL GAS GENERATOR SETS
Enclosed Units
500 KW Each Continuous duty
1 MW Total
480 volts
60 HZ
1,012 & 908 Total Run Hours


Unit #1:
Engine: Mitsubishi model # GS12A2PTK
Natural Gas Engine
Serial number 21684
Manufactured 1998 – 1999. 
Rated capacity: 500KW
Simpower model # SP0550D3Q:GS1A2-PTK
Simpower serial number: 11749
Alternator: Marathon Electric model # 572RSL4028
Serial number WA-514031-1098
Heat exchanger Simpower  model # CVR-250HRSC
Serial number 1115

Unit #2:
Engine: Mitsubishi model # GS12A2PTK
Natural Gas Engine
Serial number 216833
Rated Capacity: 500 KW
Simpower model # SP0550D3Q:GS1A2-PTK
Simpower serial number: 11749  
Alternator: Marathon Electric model # 572RSL4028
Serial number WA-514022-1098
Heat exchanger Simpower  model # CVR-250HRSC
Serial number 1116

Step-up Transformer 1:
Manufactured by GE, Rebuilt by Betz Transformers. Age, unknown
Size 500kVA
Serial number: C00524992
Primary Voltage: 12470Y/7200
Secondary Voltage: 480 Delta

Step-up Transformer 2:
Manufactured by GE, Rebuilt by Betz Transformers. Age, unknown
Size 500kVA
Serial number: C00524991
Primary Voltage: 12470Y/7200
Secondary Voltage: 480 Delta

Enclosure:
Enclosure manufactured by AlumTek Industries of Aldergrove, B.C.
Size: 20’ x 8’
with separate cooler that is 9’ x 8’
DRY WEIGHT approximately 5,500 POUNDS


PERFORMANCE CHARACTERISTICS
Standard generator sets have high performance components to meet the toughest applications.
500 KW Each Continuous duty for unlimited hours per year and 100% load factor
Newage Stamford generator ends model HC534F
with MX321 voltage regulators
- PRECISE VOLTAGE REGULATION
+ ½ % Steady State
+ 1 % from no load to full load

- PRECISE FREQUENCY CONTROL
The Woodward electronic isochronous governor has 0% droop, no load to full load, and 1/4 % steady state.

- PERMANENT MAGNET EXCITATION
Provides excellent performance with heavy SCR loads. 300% full load current available for 10 seconds during short circuit condition.

- HIGH MOTOR STARTING CAPACITY
250% of rated capacity for 10 seconds.

- LOW EMISSIONS
The Mitsubishi LeanBurn engine has low emissions without any after treatment.

CLEAN EXHAUST EMISSIONS
Emissions            G/bhp
NOx                      .7
CO                        .5
NMHC                    .2

EXCELLENT FUEL EFFICIENCY
Fuel Consumption 6800 BTU/hphr
At 100% load based on L. H. V.

Natural Gas Supply Requirements*
Gas Use Pressure (psi) % of Total Gas
Main gas                  .2 to 3 85%
Pre-chamber gas          25 to 28 15%
*Requires a maximum of 5 million BTU/hr. of pipeline quality gas at 1040 BTU/CF ± 5%.

- PARALLELING OPTIONS
Controls can be added for completely automatic.

VOLTAGE RANGE
3 WIRE
416 - 480
208 - 240
60HZ
4 WIRE
240/416 - 277/480
120/208 - 138/240

GENERATOR SET SPECIFICATIONS
60 HZ - 100% loaded
Model RM500G
KW 500
KVA 625
HP 710
BMEP 152 psi
Heat rejection to jacket water 15600 BTU/min
Heat rejection to ambient 5500 BTU/min.
Jacket water temperature 190 to 205º F
Exhaust temperature 850º F
Heat rejection to intercooler 5050 BTU/min
Exhaust gas flow 1820 SCFM
Combustion air flow 1736 CFM
Jacket water coolant flow 291 GPM

NATURAL GAS ENGINE
Mitsubishi GS12A2-PTK
Type 4 cycle, water-cooled, turbocharged, intercooled with raw water
Combustion chamber Ultra LeanBurn with pre-chamber ignition
Compression ratio 11.5:1
Engine speed 1800 RPM
Cylinder arrangement 60 degree vee 12 cylinder
Displacement 2070 cubic inch
bore, 5.91
stroke. 6.3
Exhaust flex diameter 8 inches (inside)
Muffler diameter 10 inches (inside)
Maximum exhaust back pressure 23.6 inches of water
I tltit M I 90º F t 53 GPM

STANDARD EQUIPMENT
- Mitsubishi GS12A2-PTK natural gas engine
- Newage Stamford generator (HC534F) rated for 80º C rise with 3 phase static voltage regulator (MX321) and permanent magnetic excitation. All rated per NEMA Code.
- Heavy duty structural steel subbase
- Woodward isochronous governor and air/fuel controller
- Free standing control panel with: Altronic CPU95 ignition system, automatic start/stop control, gauges for oil pressure, cylinder temp., battery voltage, water temp., running hours, AC amps, AC volts, frequency, KW, KVA, and power factor
- 24 volt automatic electric start system
- 20 amp battery charger
- Engine safety switches & Pre-alarms: low oil pressure, high water temperature, overspeed, overcrank, high exhaust temperature, low gas pressure, ignition fault
- Residential silencer with stainless steel flexible connection
- 24 volt lead acid battery, rack and cables
- Flexible fuel lines
- Catalytic converter for CO and NMHC
- Local computer with 6 screens for real time and historical data display
- Remote telephone access to local computer 

 

More Information:

Data Sheet (PDF)

   

Additional Images: (click for larger size)



1 Star2 Stars3 Stars4 Stars5 Stars (No Ratings Yet)