Cooper Superior Model 2408 Natural Gas Generator Sets Packaged by Simpson Power Products LTD 1.1 MW Each (1375 kva) 2.2 MW Total 60 Hz 480 volts 1200 RPM Total Run Hrs = 690 & 1089 Originally Shipped on 10th Day of 2000
1576 HP Originally shipped to customer from Simpower on October of 2000 Units have not operated for two years now. Used for a temporary power need. Well maintained. Functioning well at time of shutdown. Owned by a municipality. The core heaters have been kept on. Generator Info p.f. - .8 amp - 1654 Rotation - ccw rpm - 1200 phase - 3 serial - bu5l3576 gen model - mtg 846 emi - 60088300
One engine serial number is: 340399
(2) MITSUBISHI Model RM 500G - GS12A2-PTK NATURAL GAS GENERATOR SETS Enclosed Units 500 KW Each Continuous duty 1 MW Total 480 volts 60 HZ 1,012 & 908 Total Run Hours
Unit #1: Engine: Mitsubishi model # GS12A2PTK Natural Gas Engine Serial number 21684 Manufactured 1998 – 1999. Rated capacity: 500KW Simpower model # SP0550D3Q:GS1A2-PTK Simpower serial number: 11749 Alternator: Marathon Electric model # 572RSL4028 Serial number WA-514031-1098 Heat exchanger Simpower model # CVR-250HRSC Serial number 1115
Unit #2: Engine: Mitsubishi model # GS12A2PTK Natural Gas Engine Serial number 216833 Rated Capacity: 500 KW Simpower model # SP0550D3Q:GS1A2-PTK Simpower serial number: 11749 Alternator: Marathon Electric model # 572RSL4028 Serial number WA-514022-1098 Heat exchanger Simpower model # CVR-250HRSC Serial number 1116
Step-up Transformer 1: Manufactured by GE, Rebuilt by Betz Transformers. Age, unknown Size 500kVA Serial number: C00524992 Primary Voltage: 12470Y/7200 Secondary Voltage: 480 Delta
Step-up Transformer 2: Manufactured by GE, Rebuilt by Betz Transformers. Age, unknown Size 500kVA Serial number: C00524991 Primary Voltage: 12470Y/7200 Secondary Voltage: 480 Delta
Enclosure: Enclosure manufactured by AlumTek Industries of Aldergrove, B.C. Size: 20’ x 8’ with separate cooler that is 9’ x 8’ DRY WEIGHT approximately 5,500 POUNDS
PERFORMANCE CHARACTERISTICS Standard generator sets have high performance components to meet the toughest applications. 500 KW Each Continuous duty for unlimited hours per year and 100% load factor Newage Stamford generator ends model HC534F with MX321 voltage regulators - PRECISE VOLTAGE REGULATION + ½ % Steady State + 1 % from no load to full load
- PRECISE FREQUENCY CONTROL The Woodward electronic isochronous governor has 0% droop, no load to full load, and 1/4 % steady state.
- PERMANENT MAGNET EXCITATION Provides excellent performance with heavy SCR loads. 300% full load current available for 10 seconds during short circuit condition.
- HIGH MOTOR STARTING CAPACITY 250% of rated capacity for 10 seconds.
- LOW EMISSIONS The Mitsubishi LeanBurn engine has low emissions without any after treatment.
CLEAN EXHAUST EMISSIONS Emissions G/bhp NOx .7 CO .5 NMHC .2
EXCELLENT FUEL EFFICIENCY Fuel Consumption 6800 BTU/hphr At 100% load based on L. H. V.
Natural Gas Supply Requirements* Gas Use Pressure (psi) % of Total Gas Main gas .2 to 3 85% Pre-chamber gas 25 to 28 15% *Requires a maximum of 5 million BTU/hr. of pipeline quality gas at 1040 BTU/CF ± 5%.
- PARALLELING OPTIONS Controls can be added for completely automatic.
VOLTAGE RANGE 3 WIRE 416 - 480 208 - 240 60HZ 4 WIRE 240/416 - 277/480 120/208 - 138/240
GENERATOR SET SPECIFICATIONS 60 HZ - 100% loaded Model RM500G KW 500 KVA 625 HP 710 BMEP 152 psi Heat rejection to jacket water 15600 BTU/min Heat rejection to ambient 5500 BTU/min. Jacket water temperature 190 to 205º F Exhaust temperature 850º F Heat rejection to intercooler 5050 BTU/min Exhaust gas flow 1820 SCFM Combustion air flow 1736 CFM Jacket water coolant flow 291 GPM
NATURAL GAS ENGINE Mitsubishi GS12A2-PTK Type 4 cycle, water-cooled, turbocharged, intercooled with raw water Combustion chamber Ultra LeanBurn with pre-chamber ignition Compression ratio 11.5:1 Engine speed 1800 RPM Cylinder arrangement 60 degree vee 12 cylinder Displacement 2070 cubic inch bore, 5.91 stroke. 6.3 Exhaust flex diameter 8 inches (inside) Muffler diameter 10 inches (inside) Maximum exhaust back pressure 23.6 inches of water I tltit M I 90º F t 53 GPM
STANDARD EQUIPMENT - Mitsubishi GS12A2-PTK natural gas engine - Newage Stamford generator (HC534F) rated for 80º C rise with 3 phase static voltage regulator (MX321) and permanent magnetic excitation. All rated per NEMA Code. - Heavy duty structural steel subbase - Woodward isochronous governor and air/fuel controller - Free standing control panel with: Altronic CPU95 ignition system, automatic start/stop control, gauges for oil pressure, cylinder temp., battery voltage, water temp., running hours, AC amps, AC volts, frequency, KW, KVA, and power factor - 24 volt automatic electric start system - 20 amp battery charger - Engine safety switches & Pre-alarms: low oil pressure, high water temperature, overspeed, overcrank, high exhaust temperature, low gas pressure, ignition fault - Residential silencer with stainless steel flexible connection - 24 volt lead acid battery, rack and cables - Flexible fuel lines - Catalytic converter for CO and NMHC - Local computer with 6 screens for real time and historical data display - Remote telephone access to local computer